    利用焓差实验室对一种户式温湿分控空调机组的设备显热比变化特性进行实验.分别保持通过该机组两侧蒸发器的换热介质的入口参数恒定不变,当压缩机转速和风侧蒸发器的冷剂比例同时变化时,得到设备制冷量、设备显热比SCR以及能效比EER的变化曲线.实验结果表明,改变机组压缩机转速以及风侧冷剂的比例,不但改变机组总制冷量,同时改变机组输出显热冷量与潜热冷量的比例;设备SCR的变化范围0.6~1.0,远远大于传统空调机组的变化范围,可以与房间显热比SHR值更好地匹配,以更好地控制室内热环境.同时表明,设备SCR的调控受到机组总冷量与能效比的限制,在实现设备SCR及总制冷量的前提下,尽量使EER值最大,有利于节能.

    Abstract:

    An experimental study was made of the change characteristics of sensible cooling ratio of the residential temperature humidity independent control air conditioning. The experiment was made in the enthalpy potential laboratory and the parameters value of heat exchange medium that filled in two evaporators were remained unchanged. By changing the compressor speed and the refrigerant distribution ratio, the curves of cooling capacity, sensible cooling ratio SCR and the energy efficiency ratio EER could be obtained. The experimental results indicate that not only the total cooling capacity, but the ratio of the sensible and latent heat handling capacity can be changed. The range of SCR is from 0.6 to 1.0, which is much more than the traditional air conditioning. It means that it can match the room sensible heat ratio (SHR) and control the indoor thermal environment better. Meanwhile, SCR is restricted by the total cooling capacity and EER. For saving energy, EER should be maximized on the basis of the realization of the cooling capacity and SCR.

    参考文献
    相似文献
    引证文献
引用本文

刘畅,张旭,刘金涛.户式温湿分控空调机组运行特性实验[J].同济大学学报(自然科学版),2014,42(11):1705~1710

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2013-12-15
  • 最后修改日期:2014-07-21
  • 录用日期:2014-06-04
  • 在线发布日期: 2014-11-07
  • 出版日期: