Impact of Plenum on Air Distribution and Thermal Stratification in Underfloor Air Distribution System
CSTR:
Author:
Affiliation:

Department of Building Services Engineering,The Hong Kong Polytechnic University,School of Mechanical Engineering, Tongji University,School of Mechanical Engineering, Tongji University,Shanghai Academy of Building Research

Clc Number:

TU834.1

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    The real performance of under floor air distribution (UFAD) system in the office was studied by focusing on the impact of plenum on the indoor air motion and thermal stratification. The practical thermal stratification in an office with under floor plenum was tested first. Numerical simulation was adopted to quantificationally analyze the impact of heat gains in the plenum on the indoor thermal environment. The results show that the air in the plenum undertakes approximately 40% of indoor cooling load. The supply air temperature from air diffusers increases, leading to the decay of thermal stratification. The increase of flow rate will decrease the vertical temperature gradient as well. More attention should be paid to the influence of plenum on indoor thermal balance and flow field. The advantage of UFAD system depends on the good sealing and thermal insulation measure at the raised floor.

    Reference
    Related
    Cited by
Get Citation

NIU Jianlei, SHEN Chong, GAO Naiping, DONG Kun. Impact of Plenum on Air Distribution and Thermal Stratification in Underfloor Air Distribution System[J].同济大学学报(自然科学版),2014,42(3):0454~0459

Copy
Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:April 09,2013
  • Revised:November 26,2013
  • Adopted:October 09,2013
  • Online: March 10,2014
  • Published:
Article QR Code