Effect of Channel Structure for Board Economizer on Heat Transfer Characteristics
CSTR:
Author:
Clc Number:

TK172

  • Article
  • | |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • | |
  • Comments
    Abstract:

    The heat transfer characteristics of allwelded plate economizer in different structure parameters and flue gas velocities were numerically simulated using Fluent and experimentally verified. The results show that the whole welding type plate heat exchanger whose major axis of the ellipse is 30 mm has the highest heat transfer coefficient, when the ratio of the shortlong shaft is 0.6, the flow path in interboard spacing of flue gas is controlled at 15 mm, and the rate of flue gas flowing is in 8 m?s-1. The highest heat transfer coefficient is about 50 W?(m2?K)-1.

    Reference
    Related
    Cited by
Get Citation

WU Lijun, YUAN Zhicheng, WANG Xiaoliu, JU Guidong. Effect of Channel Structure for Board Economizer on Heat Transfer Characteristics[J].同济大学学报(自然科学版),2016,44(8):1248~1252